Conduit Fill Calculator

EMT or PVC Schedule 40 with THHN/THWN-2 wires — percent fill and how many wires fit.

Updated 2026-10-20 · Based on: NEC Chapter 9 Table 8 and 310.16; DIN VDE 0100-520 for metric.

How to use the Conduit Fill Calculator

  1. Choose the conduit type and trade size.
  2. Choose the wire size and count.
  3. Stay at or under 40 % fill for three or more wires.

Formula

Fill = total wire area ÷ conduit internal area (NEC Chapter 9, Tables 4 and 5).

Limits: 53 % for one wire, 31 % for two, 40 % for three or more.

Worked example

With the values preset in the calculator above:

Conduit type
EMT
Trade size
3/4
Wire size (THHN)
12
Number of wires
6
Conduit fill
14.97%
Allowed fill
40%
Max wires of this size
16
Code check
OK

Related guides

Frequently asked questions

How many 12 AWG wires in ¾ EMT?

16 THHN conductors at 40 % fill.

How many 10 AWG in ½ EMT?

5 THHN conductors.

Do ground wires count toward fill?

Yes — every conductor, including equipment grounds, counts.